Governor Model: HYG3

Following checks and corrections are applied during Validation and AutoCorrection.
- If At <= 0 then At = Mult*TimeStep
- If 0.0 < Tw < Mult*TimeStep then Tw = Mult*TimeStep
- If Pmax < Pmin then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If GV > Pmax , then Pmax = GV or if GV < Pmin , then Pmin = GV
Model Equations and/or Block Diagrams
Parameters:
Trate | Turbine rating, MW |
Pmax | Maximum gate opening, pu of mwcap |
Pmin | Minimum gate opening, pu of mwcap |
Cflag | Governor control flag, 1=PID, -1=Double Derivative |
Rgate | Steady-state droop, pu for governor output feedback |
Relec | Steady-state droop, pu, for electric power feedback |
Td | Input filter time constant, sec |
Tf | Filter time constant, sec |
Tp | Lead time constant, sec |
Velopen | Maximum gate opening velocity, pu/sec |
Velclose | Maximum gate closing velocity, pu/sec |
K1 | Double derivative gain, pu |
K2 | Double derivative gain, pu, if Cflag = -1 |
Ki | Integral gain, pu |
Kg | Gate servo gain, pu |
Tt | Power feedback time constant, sec |
db1 | Intentional deadband width, Hz |
Eps | Intentional db hysteresis, Hz |
db2 | Unintentional deadband, MW |
Tw | Water inertia time constant, sec |
At | Turbine gain, pu |
Dturb | Turbine damping coefficient, pu |
Qnl | No-load flow at nominal head, pu |
H0 | Turbine nominal head, pu |
Gv1 | Nonlinear gain point 1, pu gv |
Pgv1 | Nonlinear gain point 1, pu power |
Gv2 | Nonlinear gain point 2, pu gv |
Pgv2 | Nonlinear gain point 2, pu power |
Gv3 | Nonlinear gain point 3, pu gv |
Pgv3 | Nonlinear gain point 3, pu power |
Gv4 | Nonlinear gain point 4, pu gv |
Pgv4 | Nonlinear gain point 4, pu power |
Gv5 | Nonlinear gain point 5, pu gv |
Pgv5 | Nonlinear gain point 5, pu power |
Gv6 | Nonlinear gain point 6, pu gv |
Pgv6 | Nonlinear gain point 6, pu power |